BTU Bench

Furnace size chart by square feet

The furnace input size for houses from 800 to 3,000 sq ft in five winter climates, for 96% and 80% efficient furnaces.

Furnace size at 96% AFUE

Sq ftMildCoolColdVery coldSevere
80040,000 BTU40,000 BTU40,000 BTU40,000 BTU40,000 BTU
1,00040,000 BTU40,000 BTU40,000 BTU40,000 BTU60,000 BTU
1,20040,000 BTU40,000 BTU40,000 BTU60,000 BTU60,000 BTU
1,50040,000 BTU40,000 BTU60,000 BTU60,000 BTU80,000 BTU
1,80040,000 BTU60,000 BTU60,000 BTU80,000 BTU80,000 BTU
2,00040,000 BTU60,000 BTU60,000 BTU80,000 BTU100,000 BTU
2,40040,000 BTU60,000 BTU80,000 BTU100,000 BTU120,000 BTU
3,00060,000 BTU80,000 BTU100,000 BTU120,000 BTUTwo units or zoned

Furnace size at 80% AFUE

Sq ftMildCoolColdVery coldSevere
80040,000 BTU40,000 BTU40,000 BTU40,000 BTU60,000 BTU
1,00040,000 BTU40,000 BTU40,000 BTU60,000 BTU60,000 BTU
1,20040,000 BTU40,000 BTU60,000 BTU60,000 BTU80,000 BTU
1,50040,000 BTU60,000 BTU60,000 BTU80,000 BTU80,000 BTU
1,80040,000 BTU60,000 BTU80,000 BTU80,000 BTU100,000 BTU
2,00040,000 BTU60,000 BTU80,000 BTU100,000 BTU120,000 BTU
2,40060,000 BTU80,000 BTU100,000 BTU120,000 BTUTwo units or zoned
3,00060,000 BTU100,000 BTU120,000 BTUTwo units or zonedTwo units or zoned

Heat output needed (BTU per hour)

Sq ftMildCoolColdVery coldSevere
80012,80017,60022,40027,20033,600
1,00016,00022,00028,00034,00042,000
1,20019,20026,40033,60040,80050,400
1,50024,00033,00042,00051,00063,000
1,80028,80039,60050,40061,20075,600
2,00032,00044,00056,00068,00084,000
2,40038,40052,80067,20081,600100,800
3,00048,00066,00084,000102,000126,000

Which winter climate are you in?

  • Mild winters: Florida, Gulf Coast, south Texas, Arizona
  • Cool winters: Georgia, the Carolinas, California
  • Cold winters: Virginia, Kentucky, Missouri, Pacific NW
  • Very cold: Ohio, Illinois, Pennsylvania, New York
  • Severe: Minnesota, Wisconsin, Maine, Dakotas

The sizes are the smallest common input rating (40,000, 60,000, 80,000, 100,000 or 120,000 BTU) whose output covers the load. Many brands sell in-between sizes, so a load just above a step may fit a 70,000 or 90,000 BTU model. For your exact figure use the furnace size calculator.

Assumptions: average insulation, 8-foot ceilings. Well-insulated homes need about 15% less and older, drafty homes about 15% more. See the method on the calculator page.

Furnace size chart by square feet at 96% AFUE for mild, cold and severe climates
Save this chart for later.

Frequently asked questions

What size furnace for a 2,000 sq ft house?

About 60,000 BTU input at 96% AFUE in a cold-winter climate, and 100,000 BTU in the northern states. With an 80% furnace, 80,000 BTU and 120,000 BTU.

How many BTU furnace do I need per square foot?

About 16 BTU of heat output per square foot where winters are mild, rising to 42 in the coldest states, for a house with average insulation. Divide by AFUE for the input rating.

Why do other furnace charts show bigger sizes?

Many charts use 40 to 60 BTU per square foot regardless of insulation, which was common for older, leakier houses. Modern houses usually need less. This chart sits at the careful end; a Manual J calculation gives the real figure for your home.